XM31-915-HP - 10067220
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM31-915-HP
Firmware V2.06.0
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Float
Tamper Door closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 123.55 V
Current 2.88 A
Power 338 W
Frequency 60 Hz
Tap Status Buck tap
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 8,676 Wh
Output
Voltage 86.84 V
Power 232 W
Apparent Power 273.54 VA
Frequency 60.00 Hz
Percent Load 21.00 %
Output Setting 90 V
Output Regulation Fine
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 3.15 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Enable
Total Standby Events 42
Time Since Last Standby Event 176d 18h:01m
Time in Last Standby Event 0d 0h:01m
Total Time in Standby 371 min
Standby Events Since Reset 13
Time in Standby Since Reset 4 min
Time Since Reset 474 day(s)
Total Run Time 474 day(s)
Transformer Run Time 474 day(s)
Total Downtime 0d 0h:00m
Oil Cap Lifespan Consumed 18.8 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 14 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 
Copyright © 2017-2023 EnerSys. All Rights Reserved.