XM31-915-HP - 10067220
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM31-915-HP
Firmware V2.06.0
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Float
Tamper Door closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 122.31 V
Current 3.49 A
Power 351 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 405 Wh
Output
Voltage 87.33 V
Power 233 W
Apparent Power 283.82 VA
Frequency 59.98 Hz
Percent Load 21.60 %
Output Setting 90 V
Output Regulation Fine
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 3.25 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Enable
Total Standby Events 44
Time Since Last Standby Event 236d 19h:08m
Time in Last Standby Event 0d 0h:01m
Total Time in Standby 391 min
Standby Events Since Reset 13
Time in Standby Since Reset 4 min
Time Since Reset 534 day(s)
Total Run Time 534 day(s)
Transformer Run Time 534 day(s)
Total Downtime 0d 0h:00m
Oil Cap Lifespan Consumed 19.6 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 14 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 
Copyright © 2017-2023 EnerSys. All Rights Reserved.